Uniflair p. CO 1 Small / Medium 1 Uniflair p. CO 1 Small / Medium 1

Index 1. Introduction ………………. . . page 03 2. Technical features ……………. . page Index 1. Introduction ………………. . . page 03 2. Technical features ……………. . page 07 3. Application software. . …………………page 09 4. One possible set of hardware. . ……………page 10 5. p. CO 1 Small and Medium ………………. . page 11 6. Basic layout of the p. CO 1 medium ……. ……………page 13 7. Connecting the analogue inputs …………page 16 8. EVD 400 ……………. . …………………. page 21 9. Supervisory systems ……. . ………………. . . page 22 10. Optional features. . . …………………page 26 11. Accessories kit ……………………. page 31 2

Introduction 3 Introduction 3

Introduction: positioning in the electrical panel 4 Introduction: positioning in the electrical panel 4

Introduction The p. CO 1 series has been designed for the purpose of providing Introduction The p. CO 1 series has been designed for the purpose of providing the significant innovations introduced by the p. CO system to all those applications that require greater competitiveness in terms of price. All the p. CO 1 series controllers feature a 16 -bit microprocessor, and 2 MB flash memory (multi-language, multi-protocol). 5

Introduction The p. CO 1 controllers are available in two different sizes, according to Introduction The p. CO 1 controllers are available in two different sizes, according to the I/O and power requirements: p. CO 1 Small, p. CO 1 Medium. Some models feature an SSR to control the devices that require frequent starts and stops. 6

Technical Features • 14 MHz, 16 bit microprocessor, 16 bit internal register and operations, Technical Features • 14 MHz, 16 bit microprocessor, 16 bit internal register and operations, 512 byte internal RAM; • Up to 2 Mbyte FLASH MEMORY for the program; • 1 RS 485 serial connector for p. LAN; • Ready for connection to RS 485 supervisory network; • DIN plastic case for DIN rail installation; • 24 Vac/Vdc power supply; • Telephone connector for p. CO terminals; • Power on LED. 7

Technical Features The p. CO 1 controller is fitted with a 16 bit microprocessor Technical Features The p. CO 1 controller is fitted with a 16 bit microprocessor to run the control program, and of a set of terminals required for the connection to the controlled devices (for example: valves, compressors, fans). The program and the parameters are saved permanently in the FLASH memory, preventing data loss in the event of power failure (without requiring a backup battery). The p. CO 1 controller also allows connection to a local p. LAN network made of a series of p. CO 1 boards and terminals. Up to 10 units can be connected in the same p. LAN net 8

Application Software The power of the application software means that the user terminal allows: Application Software The power of the application software means that the user terminal allows: • the initial programming of the unit, with password-protected access to guarantee security; • the possibility to modify, at any time, the fundamental operating parameters, optionally protected by password; • the display and audible signalling (by buzzer) of any alarms; • the display of the active functions, using the LEDs; • the display of all the values measured; 9

One possible set of hardware 1. 2. User terminal with keypad, display and signal One possible set of hardware 1. 2. User terminal with keypad, display and signal LEDs; 2. p. CO 1 (SMALL version); 3. p. CO 1 (MEDIUM version); 4. connection cable between the terminal and p. CO 1; 5. connection cable between the terminal and serial printer (supplied by the customer); 6. AWG 20/22 cable for p. LAN connection between a series of p. CO 1 boards; 7. Connection terminal kit; 8. Connection to supervisor systems. 10

p. CO 1 Small and Medium PCO 1 SMALL • 8 optically-isolated digital inputs, p. CO 1 Small and Medium PCO 1 SMALL • 8 optically-isolated digital inputs, 24 Vac 50/60 Hz or 24 Vdc; • 8 digital relay outputs (1 of which with changeover contact and 2 optional SSR); • 4 analogue inputs, configurable as NTC, 0/1 V, 0/5 V, 0/20 m. A, 4/20 m. A. • 2 analogue inputs, configurable as NTC and ON-OFF • 2 x 0/10 Vdc analogue outputs. • 2 PWM outputs for phase-cutting speed controllers. 11

p. CO 1 Small and Medium PCO 1 MEDIUM • 12 optically-isolated digital inputs, p. CO 1 Small and Medium PCO 1 MEDIUM • 12 optically-isolated digital inputs, 24 Vac 50/60 Hz or 24 Vdc; • 2 optically-isolated digital inputs, 24 Vac/Vdc or 230 Vac (50/60 Hz); • 13 digital relay outputs (3 of which with changeover contact and 4 optional SSR); • 4 analogue inputs, configurable as NTC, 0/1 V, 0/5 V, 0/20 m. A, 4/20 m. A. • 2 analogue inputs, configurable as NTC and ON-OFF • 2 NTC analogue inputs • 2 x 0/10 Vdc analogue outputs. • 2 PWM outputs for phase-cutting speed controllers. 12

Basic layout of the p. CO 1 medium 13 Basic layout of the p. CO 1 medium 13

Basic layout of the p. CO 1 medium 01. Power supply connector [G (+), Basic layout of the p. CO 1 medium 01. Power supply connector [G (+), G 0 (-)] 02. 250 Vac, 2 A fuse, slow-blow (T 2 A) 03. Universal analogue inputs, NTC, 0/1 V, 0/5 V, 0/20 m. A, 4/20 m. A 04. Passive analogue inputs, NTC and ON/OFF 05. Passive analogue inputs, NTC 06. Yellow power LED and 3 signal LEDs 07. 0/10 V analogue outputs and PWM phase-cutting outputs 08. Digital inputs, 24 Vac/Vdc 09. Digital inputs, 230 Vac or 24 Vac/Vdc 10. Connector with Vref for power to 5 V ratiometric probes, and Vterm for power to ARIA terminal 11. connector for all the standard p. CO* series terminals and for downloading the application software 12. p. LAN local network connector 13. connector for the programming key 14. digital relay outputs 15. door for selecting the type of analogue inputs 16. door for inserting the serial card: • RS 485 for supervisor • RS 232 for modem interface • Gateway (protocol converter) 17. door for inserting the clock card 14

Basic layout of the p. CO 1 medium Regarding the meaning of each connector Basic layout of the p. CO 1 medium Regarding the meaning of each connector and of the correspondance between inputs – outputs, in the manual you’ll find a precise table with all the descriptions. The following table gives examples of the distribution of the inputs and outputs in relation to the 2 versions 15

Connecting the analogue inputs The analogue inputs can be configured for the more common Connecting the analogue inputs The analogue inputs can be configured for the more common sensors on the market: NTC, 0/1 V, 0/10 V, 0/20 m. A, 4/20 m. A. The different types of sensors can be selected using the corresponding dipswitches, as in the following figure. 16

Connecting the analogue inputs This is a picture taken directly from the electrical diagram Connecting the analogue inputs This is a picture taken directly from the electrical diagram inserted between the documentation at the moment of the unit delivery. In the last pages, before the components list, there is the specific dipswitches configuration. 17

Connecting the analogue inputs In this way you can: 1. Connect active temperature and Connecting the analogue inputs In this way you can: 1. Connect active temperature and humidity probes 2. Connect universal NTC temperature probes 3. Connect 4/20 m. A pressure probes 4. Connect 0/5 V ratiometric pressure probes 5. Connect the analogue inputs selected as ON/OFF 6. Connect the digital inputs 7. Connect 24 Vac digital inputs The p. CO 1 features up to 14 digital inputs for connecting safety devices, alarms, device status, remote switches. These inputs can work at 24 Vac, 24 Vdc and some at 230 Vac. 18

Connecting the analogue inputs 8. Connect the 230 Vac digital inputs The following figure Connecting the analogue inputs 8. Connect the 230 Vac digital inputs The following figure represents one of the more common Connection diagrams for the 230 Vac digital inputs. Within each group, the digital inputs are not independent: for example, with reference to Figure, the inputs ID 13 and ID 14, due to the common terminal, must be powered at the same voltage to avoid dangerous short-circuits and/or the powering of lower-voltage circuits at 230 Vac. 9. Connect the 0/10 Vdc (optoisolated) analogue outputs The zero volt must be the reference 19

Connecting the analogue inputs 10. Connect the PWM analogue outputs (for phase cutting speed Connecting the analogue inputs 10. Connect the PWM analogue outputs (for phase cutting speed controllers) 11. Connect the digital outputs (up to 13 with electromechanical relays) 20

Evd 400 The EVD 400 driver for EEV with two pole stepper motors , Evd 400 The EVD 400 driver for EEV with two pole stepper motors , is a controller that manages the electronic expansion valve. This function is achieved by optimising the opening of the valve using a PID algorithm and special control routines. The module is fitted with an Rs 485/Tlan interface for connection to a Pco 1 via Tlan protocol 21

Supervisory systems • Optional card used to interface with a HAYES standard modem. • Supervisory systems • Optional card used to interface with a HAYES standard modem. • The maximun baudrate is 19200 baud • Optional card for interfacing with an RS 485 network. • The maximun baudrate is 19200 baud 22

Supervisory systems The cards are used to interface the p. CO 1 to a Supervisory systems The cards are used to interface the p. CO 1 to a Lon. Works network. They differ by the type of interface on the Lon. Works network side: Interface to FFt-10 A 78 kbs (TPFT-10) The baudrate must be set to 4800 Interface to RS 485 39 kbs (TP 485 -39). The baudrate must be set to 4800 23

Supervisory systems p. CO Web Ethernet™ interface board Used to interface the p. CO Supervisory systems p. CO Web Ethernet™ interface board Used to interface the p. CO controllers with the BACnet™ and SNTP protocols, emerging standards in the HVAC industry • p. COWeb is an accessory for the p. CO* series products (excluding the p. COB* series) fitted with a serial port and communication via the data protocol. • p. COWeb acts a “gateway”, that is, a translator between the “Uniflair supervisor” data protocol and the Ethernet network protocols commonly used to connect the computers in a building. 24

Supervisory systems Provides communication with the TREND interface, a commonly-used building management system in Supervisory systems Provides communication with the TREND interface, a commonly-used building management system in english-speaking countries. 25

Optional Features Option that allows the management of the time and date, it and Optional Features Option that allows the management of the time and date, it and includes buffer RAM for data relating to the software application. Optional module for expanded the p. CO 1 memory (event log or Black-box features), and for the management of the time and date 26

Optional Features The cards can be used to transfer (upload ad dowload) the aplication Optional Features The cards can be used to transfer (upload ad dowload) the aplication software. The key has 2 MB flash memory. Carel supply the key with BOOT and BIOS that manage 1 MB, in this way the same key can be used with p. CO 1 contollers that have either 1 MB or 2 MB flash memory chips. 27

Optional Features This interface is used to control the main parameters of the Carel Optional Features This interface is used to control the main parameters of the Carel OEM humidifiers (water level and conductivity in the cylinder, TAM current power sensor) directly from the p. CO sistema controllers. The values read by the special sensors are converted into signals that are compatible with the inputs on the control board. The board is managed by the software application running in the p. CO controller. 28

Optional Features The expansion boards belong to the p. CO sistema family and have Optional Features The expansion boards belong to the p. CO sistema family and have been designed to increase the I/Os on the p. CO 3, p. COXS, p. CO 1, p. CO 2 controllers. A maximum of 5 expansion boards for each p. CO 3, p. COXS, p. CO 1, p. CO 2 controller can be connected. 29

Optional Features Possibility to control the same motherboard p. CO 1 with maximum 3 Optional Features Possibility to control the same motherboard p. CO 1 with maximum 3 remote user terminal. The material needed to connect them is the flat cable and the T-Derivator. For further information read the UG 40 slides. 30

Accessories / Kit Remote user terminal Serial card t. LAN, MP-Bus Clock card Serial Accessories / Kit Remote user terminal Serial card t. LAN, MP-Bus Clock card Serial card RS 485 Flooding detector standard Flooding detector+ flooding sencor additional Flooding detector + flooding sensor sensible wide External limit temperature sensor External limit humidity sensor Fire sensor Smoke sensor Fire/Smoke sensor 24 Vac relay for fire/smoke alarm centralized 31