SPECIAL PROTECTION SCHEME FOR KOODANKULAM
SPS FOR KOODANKULAM CONTINGENCY LEVEL ABOUT THE SAME AS TALCHER-KOLAR – SINGLE UNIT TRIPPING : 1000 MW – STATION LOSS : 2000 MW LARGE DIPS IN FREQUENCY LIKELY CONVENTIONAL PROTECTION SCHEMES MIGHT BE INADEQUATE LARGE INCREASE IN NORTH-SOUTH FLOWS LIKELY DUE TO TRIPPING – – – OSCILLATIONS IN THE SYSTEM REDUCED SECURITY TRUNK CORRIDOR LOADING
NLMNG CHITOOR HOODY KOLAR ALMATHI HASSAN SP-BUDUR S’HALLI HOSUR MELKOTTAIYUR MYSORE KOZHIKODE BAHOOR SALEM NEYVELI NLY-EXP ARASUR PUGALUR THRISSUR UDUMALPET SUGGESTED SPS LOAD TRIP POINTS MULTI-CIRCUIT TOWER ON 220 KV EDAMONKAYATHAR CORRIDOR TRICHY KARAIKUDI COCHIN MADURAI EDAMON TIRUNELVELI TRIVANDRUM KOODANKULAM TRANSMISSION SYSTEM AS APPROVED IN 17 TH STANDING COMMITTEE MEETING HELD AT BANGALORE IN SEP 03
SUGGESTED FEATURES SCHEME TO BE MADE PART OF THE PROJECT GRANULARITY OF SIGNAL TO BE GENERATED TO BE DECIDED – ONE SIGNAL ON ONE UNIT TRIP – SECOND SIGNAL ON BOTH UNITS TRIP SIGNAL WOULD BE TRANSMITTED THROUGH WIDEBAND TO PRE DECIDED LOCATIONS SIGNAL WOULD BE INTERPRETED BU END EQUIPMENT ND ACCORDINGLY TRIP COMMAND WILL BE ISSUED SPINNING RESERVES COULD ALSO FORM PART OF THE SCHEME AUTOMATIC RAMP UP/START UP OF SOME DEDICATED HYDRO STATIONS SAY LIKE KADAMPARAI COULD ALSO FORM PART OF THE SCHEME PROTECTION OF UNITS ON EVACUATION LINE TRIPPING (LIKE RUNBACK OF TALCHER AND KAIGA HOUSE LOADING) COULD BE PUT IN PLACE