Plant Air Wash Supply Fan EXAMPLE High Temp = ____ How to Ambient = Plant Air Wash Supply Fan EXAMPLE High Temp = ____ How to Ambient = ____ perform Temperature Rise = ____ in-house infrared trending of Electric Motors Example Report EXAMPLE SURVEY OF ELECTRIC MOTORS

High Temp Procedure for trending temperatures on Electric Motors Plant EXAMPLE • Make sure High Temp Procedure for trending temperatures on Electric Motors Plant EXAMPLE • Make sure the motor is at operating temperature (steady-state). Air Wash = ____ Ambient = ____ Temperature Rise = ____ • The first time the survey is performed, take a photograph of the motor. Take a thermograph Supply Fan (infrared picture) also, if you have an infrared (IR) camera. But you do not need an IR camera for this. If you have one - use it, but a $100 spot radiometer will do just fine. • Take a can of barbeque grill paint (E=~. 95), SAFELY clean and/or paint the points where you plan on taking the temperatures. • Enter the date. • Enter the high temperature (HT). Get the high temperature from the inboard bearing. • Enter the ambient temperature (AT). Get the ambient temperature from the motor foot or a painted spot on the floor near the motor. • The Temperature Rise (Delta-T) will automatically show in the spreadsheet and on the graph. • Put this page in a notebook (or the spreadsheet below) and take the notebook to enter the numbers each month/week/day. • If the trend is higher temperatures every time you check the motor: § Increase the frequency (say from monthly to weekly) and see if the Delta-T continues to rise and watch it closer. § Check other connected components, i. e. , outboard bearing, winding, coupling. § Add other testing, i. e. airborne ultrasonic analysis, vibration analysis, oil and wear particle analysis, eddy current analysis. General Notes: Ø Pick a temperature scale at the beginning of the trending. (Either °C - Celsius or °F - Fahrenheit and always use the same scale. Ø Keep the surface clean with an air hose, so dust does not build up on the inboard bearing and insulate it. Ø After blowing it off, give the bearing a few minutes to come back to steady state temperature. Ø This trending is predicated on the fact that the Delta-T (HT - AT = Delta-T) will not change if the motor stays in the same condition. Ø If the motor's inboard bearing gets hotter over time, something is wrong. Increase frequency and check other components. Ø The motor's inboard bearing is the pivot point of all other connected components, if something goes wrong anywhere, the bearing heats. Ø Don’t worry about being off a few degrees here or there. The idea is that you will be able to see a trend. Even if some errors are introduced, so as long as you use the same repeatable method, you will see the trend. EXAMPLE SURVEY OF ELECTRIC MOTORS

Plant #1 Air Wash #2 Spray Pump Supply Fan EXAMPLE High Temp = ____ Plant #1 Air Wash #2 Spray Pump Supply Fan EXAMPLE High Temp = ____ 125 Ambient = ____ 87 Temperature Rise = ____ 38 EXAMPLE SURVEY OF ELECTRIC MOTORS

Plant Air Wash Supply Fan EXAMPLE High Temp = ____ Ambient = ____ Temperature Plant Air Wash Supply Fan EXAMPLE High Temp = ____ Ambient = ____ Temperature Rise = ____ EXAMPLE SURVEY OF ELECTRIC MOTORS

Plant Air Wash Note: Supply Fan SAFELY clean dust/dirt from the target area before Plant Air Wash Note: Supply Fan SAFELY clean dust/dirt from the target area before recording high temp. EXAMPLE High Temp = ____ Ambient = ____ Temperature Rise = ____ EXAMPLE SURVEY OF ELECTRIC MOTORS High Temp.

122 EXAMPLE High mark where #1 Plant. Don’t put the ambient temp Temp = 122 EXAMPLE High mark where #1 Plant. Don’t put the ambient temp Temp = ____ Note: Ambient = ____ 79 Air Wash #2 it will be affected by the motor temperatures. Spray Pump Supply Fan Temperature Rise = ____ 43 EXAMPLE SURVEY OF ELECTRIC MOTORS

Plant #1 Air Wash #2 Supply Fan #2 EXAMPLE High Temp = ____ 178 Plant #1 Air Wash #2 Supply Fan #2 EXAMPLE High Temp = ____ 178 Ambient = ____ 78 Temperature Rise = ____ 100 EXAMPLE SURVEY OF ELECTRIC MOTORS

Plant #1 Air Wash #1 Supply Fan #1 EXAMPLE High Temp = ____ 107 Plant #1 Air Wash #1 Supply Fan #1 EXAMPLE High Temp = ____ 107 Ambient = ____ 76 Temperature Rise = ____ 31 EXAMPLE SURVEY OF ELECTRIC MOTORS

Plant #2 Air Wash #6 CHWP Pump Supply Fan EXAMPLE High Temp = ____ Plant #2 Air Wash #6 CHWP Pump Supply Fan EXAMPLE High Temp = ____ 147 Ambient = ____ 75 Temperature Rise = ____ 72 EXAMPLE SURVEY OF ELECTRIC MOTORS

#2 Plant # #6 Air Wash # RAF#4 A Supply Fan # EXAMPLE High #2 Plant # #6 Air Wash # RAF#4 A Supply Fan # EXAMPLE High Temp = ____ 158 Ambient = ____ 76 Temperature Rise = ____ 82 EXAMPLE SURVEY OF ELECTRIC MOTORS

#2 Plant # #6 Air Wash # RAF#4 D Supply Fan # EXAMPLE High #2 Plant # #6 Air Wash # RAF#4 D Supply Fan # EXAMPLE High Temp = ____ 158 Ambient = ____ 79 Temperature Rise = ____ 79 EXAMPLE SURVEY OF ELECTRIC MOTORS

#2 Plant # EXAMPLE #6 Air Wash # Spray Pump #4 Supply Fan # #2 Plant # EXAMPLE #6 Air Wash # Spray Pump #4 Supply Fan # High Temp = ____ 176 Ambient = ____ 78 Temperature Rise = ____ 98 EXAMPLE SURVEY OF ELECTRIC MOTORS

Plant #2 Air Wash #5 RAF#3 E Supply Fan # EXAMPLE High Temp = Plant #2 Air Wash #5 RAF#3 E Supply Fan # EXAMPLE High Temp = ____ 127 Ambient = ____ 75 Temperature Rise = ____ 52 EXAMPLE SURVEY OF ELECTRIC MOTORS

Plant #2 EXAMPLE Air Wash #5 Supply Fan #3 C High Temp = ____ Plant #2 EXAMPLE Air Wash #5 Supply Fan #3 C High Temp = ____ 147 Ambient = ____ 76 Temperature Rise = ____ 71 EXAMPLE SURVEY OF ELECTRIC MOTORS

Plant #2 Air Wash #5 RAF#3 C Supply Fan # EXAMPLE High Temp = Plant #2 Air Wash #5 RAF#3 C Supply Fan # EXAMPLE High Temp = ____ 137 Ambient = ____ 75 Temperature Rise = ____ 62 EXAMPLE SURVEY OF ELECTRIC MOTORS

Plant #2 EXAMPLE Air Wash #5 Spray Pump #3 Supply Fan # High Temp Plant #2 EXAMPLE Air Wash #5 Spray Pump #3 Supply Fan # High Temp = ____ 139 Ambient = ____ 76 Temperature Rise = ____ 63 EXAMPLE SURVEY OF ELECTRIC MOTORS

Plant Air Wash Supply Fan High Temp = ____ EXAMPLE -of-the-IRt™ State Ambient = Plant Air Wash Supply Fan High Temp = ____ EXAMPLE -of-the-IRt™ State Ambient = ____ www. stocktoninfrared Temperature Rise =. com ____ Mechanical Equipment IR P/PM Aerial Electrical Infrared on Transmission Lines Electrical Equipment IR P/PM Environmental Impact Surveys Building Heat Loss Surveys Aerial Infrared Roof Moisture Surveys Industrial Process Monitoring Structural Analysis EXAMPLE SURVEY OF 800 -248 -SCAN ELECTRIC MOTORS Typical R&D test set-up