Halton reference / Hilton Bucharest case study
Hilton Bucharest in brief § Refurbishement of the hotel kitchens this summer § The project includes § The main kitchen (of the closed type) § A show cooking area § Halton Delivered a global solution from Halton’s High Performance Kitchen concept with a promise of… 64% reduction in exhaust airflow rates… leading to 50% savings in energy consumption Hilton Bucharest case study
Hilton Bucharest in brief § The High Performance Kitchen concept solution designed for Hilton Bucharest is composed of canopies equipped with… Up to 40% reduction in exhaust airflow rates … when combined with a low velocity supply technology Capture Jet. TM technology Fire safety, hygiene and odor control … thanks to the neutralization of the grease emissions and the reduction technology Capture Ray. TM of cooking odors by UV Hilton Bucharest case study Exhaust airflow rates reduction increased to up 64% … when combined with the Capture Jet. TM M. A. R. V. E. L. technology Fire safety with any compromise on hygiene … with Halton’s factory preinstallation of fire Fire Suppression systems
Hilton Bucharest in brief Energy efficienc y Air Purification Hilton Bucharest case study IEQ Indoor Environment Quality High Performanc e Kitchen Safety
Hilton Bucharest in brief Main kitchen: 6 canopy sections 11, 750 m 3/h exhaust Hilton Bucharest case study
Hilton Bucharest in brief Show Kitchen: 4 canopy sections 6, 487 m 3/h exhaust Hilton Bucharest case study
Hilton Bucharest in brief Show kitchen 4 canopy sections 6, 487 m 3/h exhaust Main kitchen 6 canopy sections 11, 750 m 3/h exhaust Hilton Bucharest case study
Hilton Bucharest promise Our promise… Association of M. A. R. V. E. L. system & Capture Jet technology 64% reduction exhaust airflow rates Hilton Bucharest case study
Hilton Bucharest promise CJet. TM + M. A. R. V. E. L. Energy consumption 19, 598 €/year Savings 12, 592 €/year 23 months ROI Hilton Bucharest case study Capture Jet. TM Energy consumption 28, 024 €/year Savings 4, 166 €/year 5 months ROI EXHAUST only Energy consumption 32, 190 €/year Baseline
Hilton Bucharest concrete results 59, 5% reductionairflow of the rates compared to traditional systems Total exhaust in exhaust airflow main and show kitchens Reduction would have been more important if the make-up air would have been air-conditioned… in fact M. A. R. V. E. L. automatically increase the exhaust airflow rates to benefit of a higher free cooling capacity Halton: ****** solutions for hotels
Hilton Bucharest concrete results Variation in fan rotation speed 47% savings in fan power consumption compared to traditional systems The electricity consumption of a centrifugal fan is proportional to the cube of the rotation speed. Consequently, a fan that operates at 78% speed (average) has only 47% of the nominal power consumption. Halton: ****** solutions for hotels
Hilton Bucharest concrete results Indoor temperature and humidity of the main kitchen The temperature variation is limited to 2, 5°C as the humidity variation is limited to 6%. . . Showing that the system operates well thus without compromise on the capture efficiency Halton: ****** solutions for hotels