FIDEGAS Gas detection systems DURAN ELECTRONICA. Tomás Bretón 50, 28045 Madrid, Spain marketing@duranelectronica. com www. duranelectronica. com
FIDEGAS CA presentation Control unit for the detection of toxic and explosive gases provided with standard 4 -20 m. A input for 2, 4 & 8 detectors. Exclusively developed to be installed with FIDEGAS S/3 (EEx d II C T 6) detectors. Cover (keypad) in English & Spanish FIDEGAS CA is provided of: • 2 actuation levels: Prealarm and Alarm • Available outputs at 12 V DC, 230 V AC & D. C. • Alarm & cabling fault indicators • LEDs: prealarm, fault, 100% L. E. L. , auxiliary battery • Events memory Connection cable: Halogen free shield cable with 1 mm 2 section for a maximum length of 250 m. Control unit & detector EARTH connected ATEX certificate issued by Madariaga Official Laboratory LOM 03 ATEX 2095 when FIDEGAS S/3 detectors are connected. DURAN ELECTRONICA. Tomás Bretón 50, 28045 Madrid, Spain marketing@duranelectronica. com www. duranelectronica. com
FIDEGAS S/3. Exproof detectors FIDEGAS S/3 -2 Explosives available gases FIDEGAS S/3 T 1 & T 2 Toxics For other gases, consult EEx d II C T 6 DURAN ELECTRONICA. Tomás Bretón 50, 28045 Madrid, Spain marketing@duranelectronica. com www. duranelectronica. com
FIDEGAS S/3. Exproof detectors 1 1 2 maintenance Check the correct functioning of the detector with testing gas every 6 months Recalibrate FIDEGAS S/3 detector every 2 years during its working life (at manufacturer´s factory) Each filter/sensor has its own electronic circuits Do not swap sensors or circuits. DURAN ELECTRONICA. Tomás Bretón 50, 28045 Madrid, Spain marketing@duranelectronica. com www. duranelectronica. com
FIDEGAS S/3. Exproof detectors Dissassemble and replacement of FIDEGAS S/3 detector 1. Release the cables from the connector marked with 1, 2, 3, & Earth connection. 2. Releasing the self-blocking take out the whole set (cable + connector/s). 2. Release sensor´s connector. 3. Unscrew the filter/sensor. Do not twist the flat cable, neither hook it with other elements. 4. Electronic circuit can be dissassembled after releasing 2 subjection screws. Each filter/sensor has its own electronic circuit Do not swap sensors or circuits. DURAN ELECTRONICA. Tomás Bretón 50, 28045 Madrid, Spain marketing@duranelectronica. com www. duranelectronica. com maintenance
FIDEGAS CA Quick installation guide DURAN ELECTRONICA. Tomás Bretón 50, 28045 Madrid, Spain marketing@duranelectronica. com www. duranelectronica. com
FIDEGAS CA Quick installation guide 1. Mount on the wall the control unit (door to be opened from left to right). 2. Control unit´s bag includes the following replacements: 2 1 A fuses Thermal retractable tube to isolate the detector-panel shield connection cable avoiding short-circuits Conectors It allows the correct functioning of the panel when one or more are not connected (or if they has been disconnected for revisions). Screw M-4. Electronic circuit 3. Control unit – detector connection Fuse 1 A. Protect the detectors. All fault LEDs lightining up mean blowed fuse Connect: control unit-detector Isolate the shield using thermal retractable tube and connect it to EARTH in the proper connector. Place the connector in those non used connectors DURAN ELECTRONICA. Tomás Bretón 50, 28045 Madrid, Spain marketing@duranelectronica. com www. duranelectronica. com
FIDEGAS CA Quick installation guide 230 V CA Outputs Do the connection between C & NC or C & NO, being sure that the devices connected (electrovalve, contactor, siren, etc. ) work at 230 V and total consumption does not exceed the B fuse value of 2 A. Between C & NO (ALARM) Between C & NC (GAS CUT) PREALARM: This output its timed to activate the extraction during 2 minutes. IT SHOULD NOT ACTIVATE ALARMS FIDEGAS CA 2. Conector 230 V AC 12 V CC Outputs Do the connection between C & NC or C & NO, being sure that the devices connected (electrovalve, contactor, siren, etc. ) work at 2 V and total consumption does not exceed the C fuse value of 0, 5 A. Dry contact (close contact and no powered). Between C & NC (ALARM) Between C & NO (GAS CUT) Example of 12 V output connection to an electrovalve FIDEGAS CA 2. Conector 12 V DC CONSIDERATIONS: When connecting 230 V -or after a main fault- wait for 30 s before REARMING the system. Pay attention to the fuses capacity (mentioned in the manual) When all fault LEDs will be lightining up, check the state of the fuse ( D - E ) DURAN ELECTRONICA. Tomás Bretón 50, 28045 Madrid, Spain marketing@duranelectronica. com www. duranelectronica. com
FIDEGAS CA Quick installation guide FIDEGAS S/3 DETECTORS testing: 1 Put the cap on the sensor head 2 Introduce cannula In the cap´s hole Testing bottle concentration is not suitable for calibration neither precision test. 3 Release gas for 2 s. to activate alarm Ii is only recommended to check the detectors correct functioning. Wait 3 s before releasing more gas as required gas concentration to activate the ALARM keeps 2 m in the mask aprox. . DURAN ELECTRONICA. Tomás Bretón 50, 28045 Madrid, Spain marketing@duranelectronica. com www. duranelectronica. com
FIDEGAS C presentation Control unit for the detection of toxic and explosive gases for 2, 6 & 12 detectors. Exclusively developed for FIDEGAS S/10 detectors. Cover (keypad) in English & Spanish FIDEGAS C is provided with: • 2 actuation levels: Prealarm & Alarm • Available outputs at 12 V DC & 230 V AC • LEDs: Power, prealarm, output • Rearm push button • Prealarm Output FIDEGAS S/10 detector Power supply: 12 V DC Consumption: 120 m. A Type of sensor: Catalytic Useful life: 5 years Coverage area: 15 m 2 Available for: Natural gas (Methane), Butane. Propane Measurement range: From 0 to 100% L. E. L. Protection Grade: IP 435 DURAN ELECTRONICA. Tomás Bretón 50, 28045 Madrid, Spain marketing@duranelectronica. com www. duranelectronica. com
Stand-alone detectors DURAN ELECTRONICA. Tomás Bretón 50, 28045 Madrid, Spain marketing@duranelectronica. com www. duranelectronica. com
FIDEGAS C 30 presentation Stand-alone EXPROOF detector (EExd II C T 6) for explosive gases (Natural gas-Methane-, Butane-Propane, Hydrogen) provided with a relay output for acting when gas presence reaches a level equal or higher than 20% Low Explosive Limit (L. E. L. ). Available at 12 V or 24 V. Coverage area: 16 m 2 aprox. Type of sensor Alarm level Useful life Coverage area Protection grade Code of explosive atmosphere Catalityc (with synterized metal) 20% L. E. L. 4 years 16 m 2 aprox. I. P. 435 EEx d II C T 6 DURAN ELECTRONICA. Tomás Bretón 50, 28045 Madrid, Spain marketing@duranelectronica. com www. duranelectronica. com
FIDEGAS S/10 stand-alone presentation Stand-alone detector for explosive gases (Natural gas-Methane-, Butane -Propane, ) provided with a relay output for acting when gas presence reaches a level equal or higher than 20% Low Explosive Limit (L. E. L. ). Available at 12 V or 24 V. Coverage area: 16 m 2 aprox. Use shield cable 4 x 0, 25 mm 2 maximum length 300 m (4 x 0. 50 mm 2 – 600 m). Output Type of sensor Alarm level NC Catalityc 20% L. E. L. Useful life 5 years Protection grade I. P. 435 DURAN ELECTRONICA. Tomás Bretón 50, 28045 Madrid, Spain marketing@duranelectronica. com www. duranelectronica. com
applications Batteries rooms Cellars Chemical industry Chicken farms Nuclear industry Refrigeration Fertiliser plants Fumigation Grain storage Greenhouses Laboratories applications FIDEGAS CA Paper mills Water treatment Steel works Swimming pools Food processing FIDEGAS C rooms Boiler Kitchens Laboratories DURAN ELECTRONICA. Tomás Bretón 50, 28045 Madrid, Spain marketing@duranelectronica. com www. duranelectronica. com
8320efe33ab21e72d1095fb640f2b7d3.ppt