Avaya Online UPS 6000 VA Copyright© 2003 Avaya Inc. All rights reserved
Avaya Applications Advanced power protection for: – DEFINITY Communications Systems – Associated Adjunct Products – Other PBX Systems – Voice Mail Systems – Multidesktop Environment – Applications requiring extended backup time Copyright© 2004 Avaya Inc. All rights reserved 2
Key Features • Double-conversion Online Topology • Advanced Battery Management (ABM) • Extended Battery Modules (EBMs) and Cabinets (EBCs) • Rack/Tower Two-in-One Form Factor • Standard Web/SNMP Card • Hot-swappable batteries • Maintenance Bypass Switch Standard Copyright© 2004 Avaya Inc. All rights reserved 3
Complete Power Protection The 6000 VA online UPS provides double-conversion online power protection from all 9 of the most common power problems that threaten your equipment and data Power failures High voltage spikes Power sags Frequency variations Power surges Switching transients Brownouts Harmonic distortion Line noise Copyright© 2004 Avaya Inc. All rights reserved 4
Standard Configurations UPS with PPDM UPS Copyright© 2004 Avaya Inc. All rights reserved PPDM UPS with PPDM and Optional EBM UPS PPDM EBM 5
Advanced Battery Management (ABM®) Technology BC • Doubles battery service life by charging only when needed • Optimizes recharge time • Does not trickle charge and starve the electrolyte • Intelligent microprocessor controlled Only true & automatic battery check (periodic, controlled discharge) for most accurate advanced failure protection • Sleep Feature - no unnecessary battery “drain” Copyright© 2004 Avaya Inc. All rights reserved 6
ABM: 3 -Stage Charger 1. Rapid recharge to approximately 90% • Restores batteries quickly • UPS is ready for next power outage 2. Float charge to 100% • Completely charges batteries, but prevents overcharging 3. Rest mode • With charger turned off, UPS conducts accurate tests to monitor battery health and provide accurate runtime predictions Copyright© 2004 Avaya Inc. All rights reserved 7
Extended Battery Modules (EBMs) • Add up to 4 EBMs to extend backup time • Each EBM occupies only 3 U of rack space • Hot-swap capability allows you to increase backup time or replace EBMs while keeping attached equipment up and running Copyright© 2004 Avaya Inc. All rights reserved 3 U 8
Attaching EBMs Attach EBMs with a simple daisy-chain connection Connection to UPS Battery Connector for Next EBM Copyright© 2004 Avaya Inc. All rights reserved EBM 9
Extended Battery Cabinets (EBC) For battery backup times over two hours, up to 6 EBC 240 battery cabinets can be added. UPS with PPDM Copyright© 2004 Avaya Inc. All rights reserved EBC 240 10
Battery Backup Times (In Minutes) Extended Battery Modules (EBMs) Load 2000 VA/1400 W 3000 VA/2100 W 4000 VA/2800 W 5000 VA/3500 W 6000 VA/4200 W Internal Batteries 1 EBM 2 EBMs 3 EBMs 4 EBMs 38 24 19 13 10 108 70 49 37 30 186 122 86 65 52 271 178 125 96 76 362 237 168 128 102 2 EBCs 3 EBCs 4 EBCs 5 EBCs 6 EBCs 480 300 240 180 120 480 360 300 240 480 420 300 480 420 480 Extended Battery Cabinets (EBCs) Load 2000 VA/1400 W 3000 VA/2100 W 4000 VA/2800 W 5000 VA/3500 W 6000 VA/4200 W Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc. Copyright© 2004 Avaya Inc. All rights reserved 11
Rack/Tower Form Factor The 6000 VA online UPS can be installed as a tower unit or in a standard 19 -inch rack enclosure. Tower Copyright© 2004 Avaya Inc. All rights reserved Rack 12
Rack Installation Overview A separate rail kit is required for each module. The rail kit supports the UPS in a 19 -inch rack enclosure. Mounting brackets secure the UPS to the rail kit. Left rail for PPDM UPS Left rail for PPDM Mounting Brackets Copyright© 2004 Avaya Inc. All rights reserved 13
Web/SNMP Card The Web/SNMP card allows you to connect your UPS directly to an Ethernet network and the Internet. It allows you to monitor and manage your UPS with a standard web browser and SNMP, while simultaneously providing graceful shutdown for multiple computer systems over the network. Three extra hub ports Copyright© 2004 Avaya Inc. All rights reserved 14
Informative User Interface Replace Battery (ABM technology) Self-Test Overtemperature Normal Mode (UPS On) Overload Battery Mode Load Level/ Battery Level Bypass Mode Alarm Silence/Test Button Copyright© 2004 Avaya Inc. All rights reserved Site Wiring Fault Off Button On Button (Start-On-Battery) 15
Hot-swappable Batteries The UPS includes two battery trays that can be easily replaced without shutting down the connected equipment. Quick Replacement Instructions: 1 Remove front panel 2 Remove battery plate 3 Withdraw and replace battery cartridge Battery Trays (62 lb. ea. ) Copyright© 2004 Avaya Inc. All rights reserved 16
Power. Pass Distribution Modules (PPDM) The PPDM is equipped with a maintenance bypass switch so that you can replace the UPS without shutting down the connected equipment. Four different PPDMs offer different output receptacles or hardwired input/output. 3 U PPDM Bypass Switch Copyright© 2004 Avaya Inc. All rights reserved Output Receptacles 17
PPDM Selection Guide Model Number PPDM, HW SAP Input Output Voltage (Vac) Input Connection 700315104 208 -240 Hardwired NEW PPDM Copyright© 2004 Avaya Inc. All rights reserved 208 -240/120 Output Connections Hardwired (8) IEC-320 -C 13, (4) IEC-320 -C 19, (1)IEC-309 18
Optional Seismic Mounting Kit The seismic kit stabilizes the UPS in areas such as California that have earthquake safety requirements. The seismic kit holds the UPS, the PPDM, and an EBM. U-shaped brackets hold UPS in place Brackets used to bolt Kit to the floor Casters secured to base for easy movement Copyright© 2004 Avaya Inc. All rights reserved 19
Front Panel Redundant Fans User Interface UPS (5 U) Battery Trays Bypass Switch (Normal / Bypass) PPDM (3 U) Voltage Selector Switch (208/240 V) Copyright© 2004 Avaya Inc. All rights reserved 20